EC/TDS-500/600
This series of instruments are industrial on-line instruments for measuring and controlling conductivity. It applies widely to the measurement and control of pure water in the fields of pharmacy, chemical industry, electronic industry, food industry and beverage industry.
Product Details
Contact Now
Product Details
Technical Performance
EC/TDS-500 |
EC./TDS-600 |
|
maximum control output |
√ |
√ |
insulating 4-20mA/RS485 optional |
--- |
√ |
Measuring range | 0~200uS/cm□ 2000uS/cm□, 0~20mS□, 0~200mS□ 0~2000ppm□, 0~5000ppm□, |
Displaying mode | LCD |
Accuracy | 1.5%(FS) |
Stability | ±2×10-3(FS)/24h |
Working pressure | 0~0.5MPa |
Medium’s temperature | 0~50℃ |
Temperature compensation | Taking 25℃ as the datum point, digital temp. compensation |
Output Current/ Votage | insulated active output 4-20mA (≤ 500Ω) |
Control output | maximum and minimum (constantly open) contact point output. |
Capacity of contact points | 3A/AC250V (with resistant loads) |
Provided electrodes | 1.0cm-1 electrodes (0.1cm-1 constant optional) |
Length of the cable | 4.5m or otherwise agreed m |
Environmental conditions | temperature: 0~50℃ |
Humidity | ≤85%RH |
Power supply | AC 220V±10% 50/60Hz □ AC 110V±10% 50/60Hz □ |
External dimensions | 48×96×100mm (height×width×depth) |
The hole on the dial plate | 45×91mm |
The way of installation | install with a disk |
Installation
Operation Of The Instrument
4.1 Soft key function
Soft key |
Key function |
Function description |
|
Menu Key |
Under Measuring status, check or exit related parameter “setting Menu” |
|
Right shift key |
Right Shift to select the digit of the parameter, |
|
Down shift key |
Down shift to browse Menu; Change the selected parameter digital value and parameter shift |
|
Confirm key |
Confirm to select and enter into Menu and save parameter , to check the temperature value under main interface |
4.2 Main Men Interface Display
Under main interface,Press“ ”key to Menu interface, the detailed description as follows:
No. |
Menu |
Menu Content |
1 |
Un-T |
Measuring Unit: ppm /uS shift to display |
2 |
CON |
Electrode constant input |
3 |
H--C |
Relay high limit close value |
4 |
HO-- |
Relay high limit open value |
5 |
LC-- |
Relay low limit close value |
6 |
LO-- |
Relay low limit open value |
7 |
dE-- |
delay x second alarm |
8 |
4--A |
4mA corresponding conductivity value |
9 |
20-A |
20mA corresponding conductivity value |
10 |
Add-- |
RS485 address |
11 |
bAUd |
RS485 Baud rate |
12 |
CAL- |
EC Calibration Menu |
13 |
FAC- |
Factory setting |
Installation Of Measuring Electrodes
In order to make the electrodes measure correct conductivity in the pipeline, make sure to avoid data inaccuracy caused by the air bulbs or backwater in the conductance cell. Please install strictly according to the following diagram:
The way to install the pipeline
Note:
(1) The electrodes shall be installed where the position is comparatively low, the flow speed is steady and air bulbs seldom gather together.
(2)No matter horizontally installed or vertically installed, the conductance cell shall be submerged deep into the moving water.
(3) The measuring cable for measuring signals which are weak electric signals shall be separately wired, and must not be connected in the same group of wires with the power wire and control wire, so as to avoid interference
(4)If you need a longer measuring cable, please contact the manufacturer for the supply of it.
Maintenance
6.1 Measuring electrodes are accurate electrodes. You must not dismantle them or alter their shape or size, or clean them with strong acid or strong alkali, for such operations may change the constants of the electrodes and affect the accuracy of the measurement.
6.2 The measuring cables are special cables and must not be replaced at will.
6.3 The instrument shall be installed in a dry environment or control box, so as to protect it against splashing water drops or moisture and to avoid inaccurate measurement.
The Instrument As A Whole Set
Conductivity/TDS controller | 1pc |
Conductivity/TDS sensor (1.0cm-1) | 1pc |
Fixing clamp | 1 pair |
Operation manual | 1 copy |
Get in Touch
If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.
FAQS
What is EC/TDS - 500/600 and what scenarios is it used in?
How do I install the EC/TDS - 500/600 Online Controller?
How do I maintain and calibrate my EC/TDS - 500/600 controller?
EC/TDS - 500/600 Why is the measurement inaccurate?
Related Products
Related News
Apr.21,2025
Understanding Turbidity Meter Types: Which One Is Right for Your Application?
Monitoring turbidity—an indicator of water clarity—is vital for applications ranging from drinking water treatment to environmental monitoring.
Apr.21,2025
Understanding Total Dissolved Solids
Water may look clear, but that doesn’t mean it's pure. Hidden within every glass can be a range of minerals, salts, metals, and organic substances collectively known as total dissolved solids.
Apr.21,2025
Transmitter 4 20mA Technology
In the world of industrial automation and process control, accurate signal transmission is everything.
Apr.21,2025
Smart RO System Controller
In today’s world, clean water isn’t just a luxury—it’s a necessity. Whether in residential settings or industrial applications, ensuring a consistent supply of high-quality water has become vital.
Apr.21,2025
Residual Chlorine Meter is Essential
Chlorination is one of the most widely used methods for disinfecting water, whether it’s for municipal supply, swimming pools, or industrial processes.
Apr.21,2025
Essential Water Sampler Types
When it comes to environmental analysis, wastewater treatment, or drinking water inspection, water sampler types play a crucial role in collecting representative water samples for laboratory analysis.
Apr.21,2025
Dissolved Oxygen Meter
Water may look clean, but what’s happening on the molecular level often tells a different story.
Apr.21,2025
Different Types of Sensors in Industrial Automation
In the rapidly evolving age of smart manufacturing and Industry 4.0, the different types of sensors deployed across production facilities are nothing short of transformative.
If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.