Pressure Switch
The LF55 pressure switch is an automatic control device that responds to pressure signals and operates accordingly. It can serve as a safety protection measure in various devices such as pumps, hydraulic systems, and hydraulic machinery. Provide international standard mounting bracket for any part. SPDT switch ensures reliable contact switching. The pressure bellows of the standard model are phosphor bronze bellows, the pressure port is made of brass.
Product Details
Contact Now
Product Details
Introduction
Working principle
By adjusting the screw of the pressure switch, the spring tension can be adjusted. The deeper the screw is screwed in, the greater the spring force that the measuring element must overcome, and the switch point value correspondingly increases. The geometric structure of the spring is designed according to the required switching range. According to the functional principle of mechanical pressure switches, the switching point is defined by the spring pre-tension, which sets the switching point when the pressure increases. When the external pressure acts on the pressure sensing element as the pressure decreases, the spring or diaphragm deforms accordingly. When the pressure reaches a certain level, the deformation of the spring or diaphragm causes a displacement in the mechanical structure, thereby closing or opening the contacts and changing the conductivity state of the circuit.
Widely used for reverse osmosis systems.
Specification
|
120V AC |
250V AC |
|
Non-induced Current |
20A |
10A |
|
Induced Current |
Full-load |
15A |
8A |
Momentary |
72A |
Notice
Use two spanners to avoid damaging the controller; Install to the equipment by four M4 screws on back side of the controller directly; Use multi-purpose mounting plate, it is also easy to install. Please use screws in attachment bag when installing.
Model |
Range(bar) |
Differential (bar) |
Factory Setting (bar) |
Max Airtight Test |
|||
Min. |
Max. |
Min. |
Max. |
OFF |
ON |
||
LF5502 |
-0.5 |
2 |
0.2 |
0.7 |
1 |
0.5 |
16.5 |
LF5503 |
-0.5 |
3 |
0.35 |
1.5 |
2 |
1 |
16.5 |
LF5506 |
-0.5 |
6 |
0.6 |
4 |
3 |
2 |
16.5 |
LF5506M |
-0.5 |
6 |
Reset differential≤1bar |
3 |
Manual Reset |
16.5 |
|
LF5510 |
1 |
10 |
1 |
3 |
6 |
5 |
16.5 |
LF5516 |
3 |
16 |
1 |
4 |
10 |
8 |
35 |
LF5520 |
5 |
20 |
2 |
5 |
16 |
13 |
35 |
LF5530 |
8 |
30 |
Fixed 3-5 |
20 |
15~17 |
35 |
|
LF5530M |
8 |
30 |
Reset differential≤4bar |
20 |
Manual Reset |
35 |
|
LF5530D |
5 |
30 |
3 |
10 |
20 |
15 |
35 |
LF5532 |
8 |
32 |
2 |
6 |
20 |
17 |
35 |
LF5542 |
8 |
42 |
4 |
10 |
30 |
25 |
46.5 |
Scale plate:two units-“bar”&“psig”;“MPa”&“Kgf/cm2”are also available;
British thread model can add“E”according to custom requirement,
Also wilding model add“C”, capillary model add“S”,such as LF5506E;
Ammonia refrigerant model add“B”,such as LF5506B.
Dimension
Wiring Instructions
![]() |
![]() |
Pressure Switch Pictures
![]() |
![]() |
![]() |
![]() |
External Thread: G 1/4” (Standard Version) |
External Thread: 7/16-20” (Optional Version) |
Installation Picture
![]() |
![]() |
Get in Touch
If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.
FAQS
What is the main purpose of a pressure switch?
How to install pressure switching equipment?
How to operate the pressure switch correctly?
What are the causes of pressure switch failure?
Related Products
Related News
May.22,2025
Turbidity Test Fixtures: Advanced and Reliable Quality Assurance Tools
Turbidity, as an important indicator for measuring liquid transparency, is widely used in environmental monitoring, food and beverage production, pharmaceutical industry, and other fields.
May.22,2025
Total Dissolved Solids: Importance in Irrigation, Industrial Processes, and Applications
Total Dissolved Solids refers to the total content of various inorganic salts and organic matter dissolved in water, and is one of the important indicators for measuring water quality.
May.22,2025
Ro System Controller: Central nervous system in water purification systems
Reverse osmosis system, as an efficient water purification technology, has been widely used in industrial, commercial, and household fields.
May.22,2025
Residual Chlorine Meter: A Key Guarantee for Ensuring Water Quality Safety
Residual chlorine, as an important indicator in the process of water disinfection, directly affects the safety and hygiene of drinking water and various industrial water.
May.22,2025
PH oORP Controller: A Key Instrument for Water Quality Monitoring and Regulation
Water quality is an important indicator for measuring environmental health and industrial production.
May.22,2025
Dissolved Oxygen Meter: A Key Tool for Accurately Measuring Dissolved Oxygen Levels in Aquatic Environments
Dissolved oxygen is one of the important indicators for measuring water quality.
Apr.21,2025
Understanding Turbidity Meter Types: Which One Is Right for Your Application?
Monitoring turbidity—an indicator of water clarity—is vital for applications ranging from drinking water treatment to environmental monitoring.
Apr.21,2025
Understanding Total Dissolved Solids
Water may look clear, but that doesn’t mean it's pure. Hidden within every glass can be a range of minerals, salts, metals, and organic substances collectively known as total dissolved solids.
If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.